aHR0cDovL2ZyZWVzaGlwLmNvLmty
- Àü¾Ð: 220V
- ¸ðµ¨ ¹øÈ£: FLQ11
- ±Ù¿ø: CN (Á¤Ç°)
- Áõ¸í¼: ¼¼·ý
Item Description
Single-phase power surge protector installation guide
In order to ensure the safety of you and others and prevent accidents, when you install the VP-20/2P power surge protector produced by our company, please follow these steps to install the power after the power is cut off:
1. Select the appropriate installation location. Mainly installed indoors, such as a special power switch box (the box must be equipped with a 35mm wide electrical guide rail).
2. Check whether the lightning protector is damaged or missing phase? Then, in the order of hanging first and pressing back, the lightning protector is fastened to the 35mm wide electrical guide rail.
3. Wiring. The power surge protector is connected to the power supply line in parallel, and then connected to the ground network; Figure 2. When installing, the "L" and "N" flags of the lightning protector are terminated to the phase wire, and the "PE" sign is terminated to the ground wire; The wiring method is screw fastening type; The wiring sequence is to first ground the wire, and then the phase wire; The connecting wire is a multi-strand or single-stranded wire of 6 to 25mm2, and the length of the wire connecting the lightning protector and the power supply line is <
specification
Front: Wiring requirements:
The ground wire connection should use a multi-strand copper wire of not less than 6mm2, and it is required to be short, thick and straight
Please follow the signs to connect the wiring, do not connect the wrong ones
L: Phase wire
N: Connect the zero line
Indicator: Works as natural green
Ground interface
Back:
35MM mounting rails
Rails are an installation method for industrial electrical parts, and the installation of electrical components that support this standard can be easily stuck on the guide rails without being screwed, and maintenance is also very convenient
Specification
Product Name:220V Single Phase Power Surge Protector
Protection function: Power supply
Discharge current: 20KA
Working voltage: 220V
Insertion loss Ae: ¡Â 0.5dB
Response time Ta:¡Â1ns
Working temperature zone: -25¡ÆC~+85¡ÆC
Humidity¡Â95% (25-30¡ÆC)
Application: Suitable for 50Hz/60Hz, 400V and below TT, IT, TN-S, TN-C-S and other low-voltage power frequency power supply system equipotential connection, the power grid due to lightning strikes or surge voltage protection. Suitable for power protection of distribution rooms, distribution cabinets, switch cabinets, AC and DC distribution screens and other systems, building floor distribution boxes, for low voltage (220VAC) industrial power grids and civil power grids
What`s Include
220V Single Phase Power Surge Protector x1
Product pictures
|
|
|
|
|